Carrier · Heat pump troubleshooting
EXV (electronic expansion valve) check
What is going on
Check the EXV coil resistance between lead wire pairs.
Check in this order
- Turn off the outdoor unit and disconnect the power supply.
- Disconnect the EXV connectors.
- Measure the resistance between Red and Blue (Yellow), and between Brown and Orange (White).
- Red-Blue should read about 500 Ω. Other pair values are not legible in this extract.
Applies to: D5CURA EXV
More heat pump guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: D5CURA service manual, p. 64. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.