Evaporator coil temperature protection in heating
What is going on
In heating, the indoor coil protection limits a temperature offset (ΔTE1) based on room temperature T1.
Likely causes
- Room temperature T1 at or above 66°F (19°C) gives ΔTE1 = 0.
- Room temperature T1 from 59°F (15°C) to below 66°F (19°C) gives ΔTE1 = 66°F minus T1.
- Room temperature T1 below 59°F (15°C) gives ΔTE1 = 7.2°F (4°C).
Check in this order
- Measure room temperature T1 at the indoor unit.
- Apply the ΔTE1 value from the table to judge the coil protection limit.
Applies to: D5FSAA heat pump units
More heat pump guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Carrier D5FSAA product data, p. 3. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.