Evacuate using the triple evacuation method

D5CURA

What is going on

Use only if the vacuum pump cannot reach 1/4 inch and the system has no liquid water.

Check in this order

  1. Attach gauges and evacuate the system to 28 inches of mercury. Run the pump 15 minutes more.
  2. Close the service valves and shut off the pump.
  3. Connect a nitrogen cylinder and regulator. Flow nitrogen until system pressure is 2 psig.
  4. Close the service valve and let the system stand for 1 hour.
  5. Repeat the evacuation and nitrogen steps as shown in Fig. 35.
  6. Confirm the system holds a deep vacuum to show it is tight and dry.

Applies to: Refrigerant lines and indoor coil

More heat pump guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: D5CURA installation manual, p. 30. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.