Carrier · Heat pump troubleshooting
Evacuate refrigerant tubing and indoor coil (deep vacuum)
What is going on
Preferred method. Use a vacuum pump that can pull down to 1/4 inch, with a gauge that reads that depth accurately.
Check in this order
- Tighten flare nuts A, B, C and D fully.
- Connect the manifold gauge charge hose to the low side service valve charge port.
- Connect the charge hose to the vacuum pump.
- Fully open the low side of the manifold gauge.
- Start the vacuum pump and evacuate to a deep vacuum.
- Fully close the low side of the manifold gauge and stop the pump.
- Disconnect the charge hose from the low side service valve.
- Fully open service valves B and A.
- Securely tighten the service valve caps.
- Break vacuum with dry nitrogen if needed. Never use the compressor as a vacuum pump.
Applies to: Refrigerant lines and indoor coil
More heat pump guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: D5CURA installation manual, p. 29. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.