Daikin · Heat pump troubleshooting
Electronic expansion valve check (Check 12)
What is going on
Checks the EV coil and its connector and wiring.
Likely causes
- Loose EV connector
- Open EV coil
- Faulty outdoor unit main PCB
Check in this order
- Check that the EV connector is fully connected to the PCB.
- Turn the power off and back on. Listen for the EV latching sound.
- If there is no latching sound, disconnect the connector and check continuity.
- On a 5P connector, check continuity between pins 5-1, 5-2, 5-3 and 5-4. On a 6P connector, check pins 6-1, 6-2, 6-3 and 6-4.
- If a pair has no continuity, the EV coil is faulty.
- If continuity is found on the coil, the outdoor unit main PCB is faulty.
Applies to: Electronic expansion valve, 5P and 6P connector models
More heat pump guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Daikin Inverter Pair FTXM-W/V service manual SiUS042113EA, p. 148. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.