Daikin · Heat pump troubleshooting

Electronic expansion valve check (Check 12)

FTXM-W/V

What is going on

Checks the EV coil and its connector and wiring.

Likely causes

  • Loose EV connector
  • Open EV coil
  • Faulty outdoor unit main PCB

Check in this order

  1. Check that the EV connector is fully connected to the PCB.
  2. Turn the power off and back on. Listen for the EV latching sound.
  3. If there is no latching sound, disconnect the connector and check continuity.
  4. On a 5P connector, check continuity between pins 5-1, 5-2, 5-3 and 5-4. On a 6P connector, check pins 6-1, 6-2, 6-3 and 6-4.
  5. If a pair has no continuity, the EV coil is faulty.
  6. If continuity is found on the coil, the outdoor unit main PCB is faulty.

Applies to: Electronic expansion valve, 5P and 6P connector models

More heat pump guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Daikin Inverter Pair FTXM-W/V service manual SiUS042113EA, p. 148. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.