Daikin · Heat pump troubleshooting

Electrical wiring precautions

Mega-Q

What is going on

Field wiring must be done by a licensed electrician to local and national code. The inverter must be grounded properly.

Likely causes

  • Reverse phase connection.
  • Phase advancing capacitor installed.
  • Thermistor or sensor removed during wiring.
  • Ground wire connected to gas or sewage pipe.

Check in this order

  1. Do not install a phase advancing capacitor.
  2. Ground the unit as required by local and national code. Do not connect ground to gas pipes, sewage pipes, lightning rods, or telephone ground wires.
  3. Do not remove any thermistor or sensor during power or transmission wiring.
  4. If reverse phase is found, swap two of the three phases.
  5. Do not operate the unit until refrigerant piping work is finished.
  6. Attach a reverse phase or phase loss protection circuit locally if these conditions are possible.
  7. Use the specified wire and secure it with the supplied clamp. Do not put external force on terminal connections.

Applies to: Power and transmission wiring

More heat pump guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Daikin Mega-Q installation manual, p. 19. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.