Carrier · Heat pump troubleshooting
Electrical parts removal
What is going on
Procedure to remove the electrical parts in the indoor unit. Anti-static gloves must be worn.
Check in this order
- Remove 1 screw of the supporting board and remove the board.
- Remove the 2 screws of the electronic control box cover and remove the cover.
- Remove 2 screws and remove the refrigerant sensor.
- Remove the 2 screws of the electronic control box.
- Disconnect the connectors and remove the electronic control box.
- Release the 2 hooks and remove the main control board.
- Disconnect the connectors and remove 1 screw of the fan driver control board.
- Remove 1 screw and remove the reactor.
Applies to: D5FCFAH indoor unit
More heat pump guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: D5FCFAH service manual, p. 54-55. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.