Daikin · Heat pump troubleshooting

Disconnect sensors, compressor leads and valve coils (heat pump models)

DX6VSDZ6VS

What is going on

Remove the compressor leads, thermistors and valve coils. Cut the clamps as needed and note the clamp and thermistor positions for reassembly.

Check in this order

  1. Disconnect the PS connector (X17A).
  2. Disconnect the compressor connectors (U, V, W) and release the lead wires from the hooks.
  3. Remove the outdoor air thermistor, outdoor coil thermistor and defrost thermistor.
  4. Cut the 2 clamps and remove the insulation tube.
  5. Remove the suction pipe thermistor.
  6. Cut the 2 clamps on the solenoid valve coil lead wire.
  7. Remove 2 screws and take off the solenoid valve coil.
  8. Remove 1 screw and take off the four way valve coil.
  9. Cut the clamp and pull out the electronic expansion valve coil.

Applies to: 3.5 to 5.0 ton HP only

More heat pump guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Daikin SiUS612209EA service instructions, pp. 111-112. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.