Disconnect outdoor wiring on heat pump units (1.5 to 3.0 ton)

DX6VSDZ6VS

What is going on

Removal sequence for the outdoor wiring on 1.5 to 3.0 ton heat pump models. Clamps are cut during removal, so new clamps are needed on reassembly.

Check in this order

  1. Cut the 4 clamps and disconnect the PS lead wire at connector X840A. On reassembly, fix the lead to the same position with new clamps.
  2. Cut the 3 clamps. Disconnect the four way valve coil lead (connector X800A) and the solenoid valve coil lead (connector X28A).
  3. Remove 2 screws to take out the solenoid valve coil. Remove 1 screw to take out the four way valve coil. Pull out the electronic expansion valve coil. Tighten to the torque values in the valve coil setting.
  4. Remove the 3 clamps and disconnect the compressor lead wire at the U, V, W connector.
  5. Remove the outdoor air thermistor, outdoor coil thermistor and defrost thermistor. On reassembly, route the lead wires so they do not touch sharp edges.
  6. Remove the suction pipe, discharge pipe and liquid pipe thermistors. Detach the OL (overload protector) relay connector and the HPS connectors. Cut the 2 clamps and remove the insulation tube. The HPS sits inside the sound blanket (outer body).
  7. On reassembly, position the slit of the insulation tube opposite the suction pipe thermistor.

Applies to: DX6VS / DZ6VS heat pump outdoor units, 1.5 to 3.0 ton

More heat pump guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Daikin DX6VS/DZ6VS service instructions SiUS612209EB, p. 88-90. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.