Daikin · Heat pump troubleshooting
Discharge pressure check (Check No.18)
What is going on
Flow check for high discharge pressure.
Likely causes
- Dirty air filter or dirty indoor/outdoor heat exchanger
- Deformed connection pipe
- Stop valve not fully open
Check in this order
- Check whether the air filter or indoor/outdoor heat exchanger is dirty. If yes, clean it.
- Check whether the connection pipe is deformed. If yes, replace the pipe installed at site.
- Check whether the stop valve is open. If not, open it.
- If discharge pressure is still high after these checks, replace the compressor.
Applies to: Refrigerant discharge pressure
More heat pump guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Daikin Inverter Pair FTXM-W/V service manual, p. 154. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.