Daikin · Heat pump troubleshooting

Discharge pressure check (Check No.18)

FTXM-W/V

What is going on

Flow check for high discharge pressure.

Likely causes

  • Dirty air filter or dirty indoor/outdoor heat exchanger
  • Deformed connection pipe
  • Stop valve not fully open

Check in this order

  1. Check whether the air filter or indoor/outdoor heat exchanger is dirty. If yes, clean it.
  2. Check whether the connection pipe is deformed. If yes, replace the pipe installed at site.
  3. Check whether the stop valve is open. If not, open it.
  4. If discharge pressure is still high after these checks, replace the compressor.

Applies to: Refrigerant discharge pressure

More heat pump guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Daikin Inverter Pair FTXM-W/V service manual, p. 154. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.