Carrier · Heat pump troubleshooting
Delay before the compressor restarts
What is going on
Before you chase a fault, confirm whether the wait is just normal protection. On the Carrier Infinity 18VS (25VNA8) the outdoor unit deliberately holds off before the compressor starts again, and in most cases nothing is broken. The delay comes from the pressure equalizer valve cycle, from a warm-up period after power is restored, or from a fault code delay. Check the STATUS light before you tell the customer anything. Do not try to defeat protection delays beyond what the manual allows.
Likely causes
- Pressure equalizer valve cycle after every compressor stop
- 10-minute warm-up after high voltage power-up
- Protection delays from fault codes
- Brown-out recovery delay after a low voltage event
Check in this order
- After every compressor stop the pressure equalizer valve opens for 150 s, then 15 s off before the next start, this cannot be bypassed
- After power-up the compressor sump warms for 10 minutes (code 68)
- Check the STATUS light for any other fault delay and look the code up
- The brown-out recovery delay can be cleared using the Forced Defrost pins as the manual describes, confirm line voltage is good and follow the unit literature exactly
- If the delays keep repeating, check supply voltage at the unit for dips
- Explain the normal wait to the homeowner so it is not mistaken for a fault
Applies to: Carrier Infinity 18VS variable speed heat pump 25VNA8
More heat pump guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Carrier 25VNA8 / 24VNA9 Service Manual, Timing / delays p.8. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.