Carrier · Heat pump troubleshooting

Defrost mode entry and exit

D5FCFA

What is going on

Defrost starts when any entry condition is met and ends when a defrost end condition is met. Symbols TCDI1, TCDI2, TCDI3, TCDE1 and TCDE2 are not defined on these pages, so use the values in the controller data.

Likely causes

  • Frost build-up on the outdoor coil in heating
  • Outdoor coil temperature T3 falls below defrost thresholds

Check in this order

  1. Record the minimum T3 from minute 10 to minute 15 after compressor start (T30).
  2. Expect defrost after 29 min if T3 is below TCDI1 and T3 plus the SUB offset is at or below T30.
  3. Expect defrost after 35 min if T3 is below TCDI2 and T3 plus the SUB offset is at or below T30.
  4. Expect defrost after 29 min if T3 stays below TCDI3 for 3 minutes.
  5. Expect defrost after 120 min if T3 is below 5°F (-15°C).
  6. End defrost when T3 rises above TCDE1, or stays above TCDE2 for 80 seconds, or defrost has run 10 minutes.

Applies to: D5FCFAH

More heat pump guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: D5FCFAH service manual, p. 18. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.