Defrost mode entry and exit
What is going on
Defrost starts when any entry condition is met and ends when a defrost end condition is met. Symbols TCDI1, TCDI2, TCDI3, TCDE1 and TCDE2 are not defined on these pages, so use the values in the controller data.
Likely causes
- Frost build-up on the outdoor coil in heating
- Outdoor coil temperature T3 falls below defrost thresholds
Check in this order
- Record the minimum T3 from minute 10 to minute 15 after compressor start (T30).
- Expect defrost after 29 min if T3 is below TCDI1 and T3 plus the SUB offset is at or below T30.
- Expect defrost after 35 min if T3 is below TCDI2 and T3 plus the SUB offset is at or below T30.
- Expect defrost after 29 min if T3 stays below TCDI3 for 3 minutes.
- Expect defrost after 120 min if T3 is below 5°F (-15°C).
- End defrost when T3 rises above TCDE1, or stays above TCDE2 for 80 seconds, or defrost has run 10 minutes.
Applies to: D5FCFAH
More heat pump guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: D5FCFAH service manual, p. 18. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.