Carrier · Heat pump troubleshooting

DC fan motor check (indoor and outdoor)

D5FUHA

What is going on

Check the fan motor supply and control signals. Indoor DC fan motors have the control chip in the motor. Outdoor DC fan motors have the control chip in the outdoor PCB.

Likely causes

  • Faulty fan motor
  • Faulty fan motor control chip or PCB

Check in this order

  1. Indoor fan with power on and unit in standby, measure the voltage between pin 1 and pin 3, and between pin 4 and pin 3 at the fan motor connector.
  2. Indoor fan if the voltage is not in the range in the pin table, replace the PCB.
  3. Outdoor fan shut off power and release the UVW connector.
  4. Outdoor fan measure the resistance of U-V, U-W and V-W.
  5. Outdoor fan if the three resistances are not equal, replace the fan motor.
  6. Outdoor fan if they are equal, replace the PCB.

Applies to: D5FUHA

More heat pump guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: D5FUHA service manual, p. 26. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.