Carrier · Heat pump troubleshooting

Crossover wiring to single or two stage furnace (KSAIC0701230 interface)

D5CURA

What is going on

Pairing an approved residential furnace with the D5CURA through the crossover interface. Only crossover outdoor units (D5CURA/D5CUHA) are compatible.

Check in this order

  1. Install the KSAIC0701230 crossover interface between the thermostat, furnace control and outdoor unit.
  2. Wire 24 VAC field wiring to the interface and the furnace leak dissipation board as shown on page 21.
  3. Make sure the heat pump has a high pressure switch for dual fuel use.
  4. Use a dual fuel thermostat. Simultaneous heat pump and furnace operation is not permitted.
  5. Do not use the W terminal on the interface for dual fuel use or where emergency heat is wanted.
  6. Do not use any 24 V terminals on the outdoor unit.
  7. The outdoor reversing valve still energizes in heat pump heating. Set the O to energize-in-cool logic so airflow matches Y1 and Y/Y2 demands.
  8. The furnace leak dissipation logic triggers a leak detection error on the interface display through the alarm input. Refer to the interface display for the code.

Applies to: D5CURA with approved furnaces via KSAIC0701230

More heat pump guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: D5CURA installation manual, p. 21. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.