Carrier · Heat pump troubleshooting
Crossover wiring to single or two speed fan coil (KSAIC0701230 interface)
What is going on
Pairing an approved fan coil with the D5CURA through the crossover interface. Only crossover outdoor units (D5CURA/D5CUHA) are compatible.
Check in this order
- Install the KSAIC0701230 crossover interface between the thermostat, fan coil control and outdoor unit.
- Wire 24 VAC field wiring to the interface and fan coil leak dissipation board as shown on page 22.
- Make sure the heat pump has a high pressure switch for dual fuel use.
- Use a dual fuel thermostat. Simultaneous heat pump and furnace operation is not permitted.
- Do not use any 24 V terminals on the outdoor unit.
- Do not use the W terminal on the interface for dual fuel use or where emergency heat is wanted.
- The outdoor reversing valve still energizes in heat pump heating. Set the O to energize-in-cool logic so airflow matches Y1 and Y/Y2 demands.
- The fan coil leak dissipation logic triggers a leak detection error on the interface display through the alarm input. Refer to the interface display for the code.
Applies to: D5CURA with approved fan coils via KSAIC0701230
More heat pump guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: D5CURA installation manual, p. 22. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.