Daikin · Heat pump troubleshooting

Cooling emergency mode - EEV cased coil

DX6VS / DZ6VS Inverter outdoor units with CHPE EEV cased coils

What is going on

Cooling runs with the gas furnace or modular blower providing airflow. The cooling level is picked at the outdoor unit.

Check in this order

  1. Turn off power to all equipment.
  2. Remove thermostat communication wires (1, 2, R, C) from all connected units and from the thermostat.
  3. Reconnect the wires to the communication terminal of the gas furnace or modular blower and short-circuit it so the furnace or blower runs alone. Check its service manual for the wiring points.
  4. Set the cased coil DS-6 S-21 to ON and S-22 to OFF for cooling emergency mode.
  5. Select the cooling level on outdoor DS-2 S-1 and S-2 (Low, Medium or High). See the DS-2 table.
  6. Reconnect the emergency wiring to the furnace or blower communication terminal BEFORE setting outdoor DS-2. Otherwise the compressor may be damaged.
  7. Power the equipment on. Cooling emergency starts.
  8. When communication is re-established, set the switches back to default and restore all thermostat wiring.

Applies to: CHPE cased coil with gas furnace or modular blower

More heat pump guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Daikin SiUS612209EA service instructions, p. 34. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.