Daikin · Heat pump troubleshooting

Cooling analysis chart

DX6VSDZ6VS

What is going on

Use the readings to find the likely cause. Normal outdoor range for cooling analysis is 67-115 F. Normal indoor range is 65-85 F. Readings that fall outside the limits point to the causes below.

Likely causes

  • Discharge temperature above 200 F or below 105 F
  • Discharge superheat above 70 F or below 20 F
  • High pressure above 490 psig or below 255 psig
  • Outdoor SSV superheat above 20 F or below 4 F
  • Low pressure above 185 psig or below 100 psig
  • Repeated stop/start, weak cooling, no switch cooling, noise, or stop operation
  • Stop valve not fully open, line set restriction or too long, blocked filter-dryer, EEV or sensor faults, dirty coils, recirculation, out-of-range ambient, non-condensable gas, fan or compressor failure, over or under charge, leak, control board failure, low indoor CFM

Check in this order

  1. Fully open the liquid and gas stop valves.
  2. Check the line set for restriction and length. Change OD position if needed.
  3. Replace the filter-dryer if it is blocked.
  4. Check the EEV, sensors and coils. Repair or replace as needed.
  5. Re-arrange OD or ID position if recirculation is present.
  6. Clean dirty outdoor or indoor heat exchangers.
  7. Recover refrigerant, evacuate and recharge if non-condensable gas is present.
  8. Recover part of the charge if overcharged; test for leaks and add refrigerant if undercharged.
  9. Specify and repair any leak point.
  10. Check airflow trim and the ID fan motor if CFM is low.

Applies to: DX6VS/DZ6VS outdoor unit, cooling mode

More heat pump guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Daikin DX6VS/DZ6VS outdoor unit installation manual, p. 41. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.