Daikin · Heat pump troubleshooting

Cooling analysis chart: possible causes and remedies

DX6VS / DZ6VS

What is going on

Use the cooling analysis chart when the unit shows high or low discharge temperature, pressure or superheat, repeated stop/start, weak cooling, no cooling, or noise. Normal cooling range: outdoor 67-115 F, indoor 65-85 F.

Likely causes

  • Liquid stop valve not fully open
  • Gas stop valve not fully open
  • Line set restriction
  • Line set too long
  • Blocked filter-dryer
  • Indoor EEV coil failure
  • Indoor EEV failure
  • Outdoor solenoid valve coil failure
  • Outdoor solenoid valve failure
  • High pressure switch failure
  • Pressure sensor failure
  • Outdoor suction thermistor failure
  • Outdoor discharge thermistor failure
  • Outdoor coil thermistor failure
  • Outdoor air thermistor failure
  • Outdoor air recirculation
  • Indoor air recirculation
  • Dirty outdoor heat exchanger
  • Dirty indoor heat exchanger
  • Outdoor ambient temperature too high or too low
  • Indoor return air temperature too high or too low
  • Non-condensable gas in system
  • Outdoor fan motor failure
  • Overcharge
  • Undercharge
  • Refrigerant leak
  • Outdoor control board failure
  • Indoor unit failure
  • Compressor failure
  • Compressor and gas furnace running at the same time
  • Cooling loop not attached to cold plate
  • Cooling loop grease insufficient
  • Low indoor CFM

Check in this order

  1. Fully open the liquid stop valve.
  2. Fully open the gas stop valve.
  3. Check the line set for restriction; check line set length and change outdoor position if needed.
  4. Replace the filter-dryer if blocked.
  5. Check the indoor EEV coil connection to the control board; repair or replace if needed.
  6. Check the indoor EEV; replace or repair if needed.
  7. Check the outdoor solenoid valve coil connection; repair or replace if needed.
  8. Check the outdoor solenoid valve; replace or repair if needed.
  9. Check the high pressure switch resistance; replace if needed.
  10. Check the pressure sensor resistance and connections; replace if needed.
  11. Check the outdoor suction, discharge, coil and air thermistors for resistance and connections; replace if needed.
  12. Re-arrange the outdoor unit position if air is recirculating.
  13. Re-arrange the indoor unit position if air is recirculating.
  14. Clean the outdoor heat exchanger.
  15. Clean the indoor heat exchanger.
  16. Recover refrigerant, evacuate the pipe and recharge if non-condensable gas is present.
  17. Replace the outdoor fan motor if it has failed.
  18. Recover part of the charge if overcharged.
  19. Test for leaks and add refrigerant if undercharged.
  20. Find and repair the leak point.
  21. Replace the outdoor control board if it has failed.
  22. Replace the indoor unit if it has failed.
  23. Replace the compressor if it has failed.
  24. Attach the cooling loop to the cold plate.
  25. Add grease to the cooling loop if insufficient.
  26. Check airflow trim and indoor fan motor; repair or replace if needed.

Applies to: DX6VS / DZ6VS heat pump in cooling

More heat pump guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Daikin DX6VS / DZ6VS service instructions SiUS612209EA, p. 12. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.