Connecting the refrigerant pipes at the units

D5CURA

What is going on

Connect the indoor unit first, then the outdoor unit, always low-pressure line first.

Likely causes

  • Over-tightening can damage the flare. Under-tightening can leak.

Check in this order

  1. Connect the copper pipes to the indoor unit first.
  2. Connect the pipes to the outdoor unit next.
  3. Connect the low-pressure line first, then the high-pressure line.
  4. Put a thin coat of refrigeration oil on each flared end.
  5. Align the two pipe centres.
  6. Tighten the flare nut by hand.
  7. Hold the unit fitting with a wrench and tighten the nut to the Table 9 torque with a torque wrench.
  8. After indoor connection, bind the power cable, signal cable and piping together with tape.

Applies to: Indoor and outdoor unit flare connections

More heat pump guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Carrier D5CURA installation manual, p. 14. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.