Carrier · Heat pump troubleshooting
Connect the inverter test tool (Dr. SMART) to the outdoor unit
What is going on
The inverter test tool connects to the existing cable on the outdoor unit test port. The Dr. SMART tool connects to the white terminal.
Check in this order
- Shut off the power and remove the electrical panel.
- Find the cable already connected to the test port on the outdoor unit.
- Disconnect the female end from the port and connect the test tool to that cable with the connector supplied with the tool.
- Connect the Dr. SMART tool to the white terminal as shown in the manual figures.
- After the maintenance is finished, plug the female end back into the port.
Applies to: D5FCFAH outdoor unit inverter
More heat pump guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Carrier D5FCFAH service manual, p. 29. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.