Compressor wiring and thermistor removal (3.5 to 5.0 ton HP)
What is going on
Disconnecting compressor power and removing the outdoor air, outdoor coil, defrost and suction pipe thermistors on heat pump models.
Check in this order
- Disconnect the PS connector (X17A).
- Disconnect the compressor leads at U, V and W, and release them from the hooks.
- Remove the outdoor air thermistor, outdoor coil thermistor and defrost thermistor. Thermistor positions differ between 3.5/4.0 ton and 5.0 ton units.
- Cut the 2 clamps and remove the insulation tube.
- Remove the suction pipe thermistor.
- On reassembly, position the slit in the insulation tube opposite the suction pipe thermistor.
Applies to: 3.5 to 5.0 ton HP outdoor units
More heat pump guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Daikin DX6VS/DZ6VS service instructions SiUS612209EB, pp. 111-112. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.