Daikin · Heat pump troubleshooting
Compressor overload (OL activation), code E5
What is going on
Compressor overload is detected through the compressor OL. The system shuts down if the error repeats. Reset occurs after about 60 minutes of continuous run without another error. OL (Q1M) activating temperature is 120 to 130°C (248 to 266°F). Recovery temperature is 105°C (221°F).
Likely causes
- Discharge pipe thermistor disconnected or defective
- Connector S40 disconnected
- Two terminals of OL (Q1M) disconnected
- Defective OL (Q1M) or broken OL harness
- Defective electronic expansion valve or coil
- Defective four way valve or coil
- Defective outdoor unit PCB
- Refrigerant shortage
- Water mixed in refrigerant
- Defective stop valve
Check in this order
- Turn off the power switch before connecting or disconnecting any connector.
- Check whether the discharge pipe thermistor is disconnected. If so, insert it in position. If the thermistor is faulty, replace it. See Check No. 01 (P.141).
- Check that connector S40 is properly connected. If not, reconnect it.
- Disconnect connector S40 from the PCB and measure the resistance across its two terminals. Nearly 0 Ω is normal.
- Disconnect the two terminals of OL (Q1M) and measure its resistance. Nearly 0 Ω is normal. If faulty, replace the OL (Q1M) or the OL harness.
- Check the electronic expansion valve. See Check No. 12 (P.143). Replace the valve or its coil if faulty.
- Check the four way valve. See Check No. 13 (P.144). Replace the valve or its coil if faulty.
- Check the refrigerant line for shortage, water contamination and stop valve position. See Check No. 14 (P.145). Correct any refrigerant shortage, water mixed in refrigerant or closed stop valve.
- If all checks are normal, replace the outdoor unit PCB (main PCB).
Applies to: Inverter pair wall mounted FTXM-W/V, compressor overload circuit
More heat pump guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Daikin FTXM-W/V service manual SiUS042113EA, p. 118. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.