Daikin · Heat pump troubleshooting

Compressor insulation resistance test (S-17A)

DX6VSDZ6VS

What is going on

The inverter on the outdoor control board reads the position signal from the UVW lines to the compressor. Use this test when the system reports a compressor fault.

Likely causes

  • Insulation breakdown between compressor terminal and housing
  • Wiring error on UVW terminals

Check in this order

  1. Disconnect all power.
  2. Remove the leads from the compressor terminals. Follow the S-17 warnings before removing the terminal cover.
  3. Check the UVW wiring connection on the compressor terminals (label on top of compressor).
  4. Measure insulation resistance between the compressor terminal and unpainted refrigerant piping.
  5. If the reading is anything other than infinity, replace the compressor.

Applies to: Outdoor units DX6VS / DZ6VS, 1.5-5.0 ton

More heat pump guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Daikin SiUS612209EA service instructions, p. 20. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.