Daikin · Heat pump troubleshooting
Compressor insulation resistance test (S-17A)
What is going on
The inverter on the outdoor control board reads the position signal from the UVW lines to the compressor. Use this test when the system reports a compressor fault.
Likely causes
- Insulation breakdown between compressor terminal and housing
- Wiring error on UVW terminals
Check in this order
- Disconnect all power.
- Remove the leads from the compressor terminals. Follow the S-17 warnings before removing the terminal cover.
- Check the UVW wiring connection on the compressor terminals (label on top of compressor).
- Measure insulation resistance between the compressor terminal and unpainted refrigerant piping.
- If the reading is anything other than infinity, replace the compressor.
Applies to: Outdoor units DX6VS / DZ6VS, 1.5-5.0 ton
More heat pump guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Daikin SiUS612209EA service instructions, p. 20. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.