Daikin · Heat pump troubleshooting
Compressor insulation resistance test (inverter compressor)
What is going on
The inverter takes its position signal from the UVW lines to the compressor. Use this test when the system flags a compressor malfunction. Compressor terminal covers must be in place and secured before and after the test.
Likely causes
- Insulation breakdown between compressor terminal and housing
Check in this order
- Disconnect all power. Remove the leads from the compressor terminals, observing the terminal cover warnings.
- Check the UVW wiring at the compressor terminals (labels are on top of the compressor).
- Measure insulation resistance between the compressor terminal and unpainted refrigerant piping.
- If the reading is anything other than infinity, replace the compressor.
Applies to: Inverter compressor on outdoor unit
More heat pump guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Daikin DX6VS/DZ6VS service instructions SiUS612209EB, p. 20. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.