Compressor ground test
What is going on
Use when a breaker or fuse has tripped. A trip indicates an electrical fault that must be found. The circuit protective device rating must match the nameplate.
Likely causes
- Compressor winding grounded to housing
- Damaged lead wires or insulation
Check in this order
- If a breaker or fuse trips, the terminal cover in place allows one reset or fuse replacement only. If it trips again, do not reset.
- Disconnect all power, making sure all legs are open.
- Without removing the terminal cover, disconnect the three compressor leads at the nearest point.
- With the ohmmeter on the highest resistance scale (R x 10,000 or higher), check each lead to ground (for example an unpainted tube on the compressor).
- If a ground is indicated, remove the terminal cover and inspect for loose leads or broken insulation.
- If nothing is visible, remove the leads at the compressor terminals carefully, then retest each terminal to ground.
- If ground is still indicated, replace the compressor. Reading should be infinity.
Applies to: Compressor leads on outdoor unit
More heat pump guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Daikin DX6VS/DZ6VS service instructions SiUS612209EB, p. 21. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.