Daikin · Heat pump troubleshooting

Compressor ground test

DX6VSDZ6VS

What is going on

Use when a breaker or fuse has tripped. A trip indicates an electrical fault that must be found. The circuit protective device rating must match the nameplate.

Likely causes

  • Compressor winding grounded to housing
  • Damaged lead wires or insulation

Check in this order

  1. If a breaker or fuse trips, the terminal cover in place allows one reset or fuse replacement only. If it trips again, do not reset.
  2. Disconnect all power, making sure all legs are open.
  3. Without removing the terminal cover, disconnect the three compressor leads at the nearest point.
  4. With the ohmmeter on the highest resistance scale (R x 10,000 or higher), check each lead to ground (for example an unpainted tube on the compressor).
  5. If a ground is indicated, remove the terminal cover and inspect for loose leads or broken insulation.
  6. If nothing is visible, remove the leads at the compressor terminals carefully, then retest each terminal to ground.
  7. If ground is still indicated, replace the compressor. Reading should be infinity.

Applies to: Compressor leads on outdoor unit

More heat pump guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Daikin DX6VS/DZ6VS service instructions SiUS612209EB, p. 21. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.