Daikin · Heat pump troubleshooting

Compressor ground test (S-17B)

DX6VSDZ6VS

What is going on

A tripped fuse or breaker means an electrical problem exists. Check that the breaker or fuse rating matches the nameplate before resetting.

Likely causes

  • Compressor winding grounded to housing
  • Damaged lead insulation at the compressor

Check in this order

  1. If a fuse or breaker tripped, replace the fuse or reset the breaker one time only. If it trips again, do not reset.
  2. Disconnect all power and make sure all legs are open.
  3. Do not remove the terminal cover. Disconnect the three compressor leads at the nearest point.
  4. Using an ohmmeter on the highest resistance scale (R x 10,000 or higher), check each lead to ground (such as an unpainted tube).
  5. If a ground is indicated, remove the terminal cover and check for loose leads or broken insulation.
  6. If no visible fault, remove the leads at the compressor terminals and retest each terminal to ground.
  7. If there is any reading, the compressor is defective. Replace it. Expect infinity.

Applies to: Outdoor units DX6VS / DZ6VS

More heat pump guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Daikin SiUS612209EA service instructions, p. 21. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.