Daikin · Heat pump troubleshooting
Compressor ground test (S-17B)
What is going on
A tripped fuse or breaker means an electrical problem exists. Check that the breaker or fuse rating matches the nameplate before resetting.
Likely causes
- Compressor winding grounded to housing
- Damaged lead insulation at the compressor
Check in this order
- If a fuse or breaker tripped, replace the fuse or reset the breaker one time only. If it trips again, do not reset.
- Disconnect all power and make sure all legs are open.
- Do not remove the terminal cover. Disconnect the three compressor leads at the nearest point.
- Using an ohmmeter on the highest resistance scale (R x 10,000 or higher), check each lead to ground (such as an unpainted tube).
- If a ground is indicated, remove the terminal cover and check for loose leads or broken insulation.
- If no visible fault, remove the leads at the compressor terminals and retest each terminal to ground.
- If there is any reading, the compressor is defective. Replace it. Expect infinity.
Applies to: Outdoor units DX6VS / DZ6VS
More heat pump guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Daikin SiUS612209EA service instructions, p. 21. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.