Daikin · Heat pump troubleshooting

Compressor burnout check and cleanup

DX6VSDZ6VS

What is going on

A burnout forms acids and sludge. Confirm it with an oil acid test before doing a full cleanup.

Likely causes

  • Compressor overheating and decomposition of oil and motor insulation

Check in this order

  1. Attach a hose to the liquid line drill valve and recover refrigerant properly, following EPA rules.
  2. Remove the compressor and take an oil sample from the gas stub.
  3. Run an oil acid test kit. If the oil is not acidic, no complete cleanup is needed.
  4. If acid level is unacceptable, clean the system with the clean-up drier method.
  5. Keep sludge and oil away from skin.

Applies to: Compressor burnout

More heat pump guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Daikin DX6VS/DZ6VS service instructions SiUS612209EB, p. 23. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.