Cold climate outdoor unit location

DX6VS / DZ6VS FIT

What is going on

Install the unit so snow and drain water cannot block the coil or freeze the base.

Check in this order

  1. Mount the unit on a field-supplied stand so the bottom frame is more than 19 3/4 in. (500 mm) above expected snowfall.
  2. Fit a snow hood and snow visor (field supplied).
  3. Do not put the unit where snowdrift forms.
  4. Use a drain pan heater where outdoor air drops below 32°F (0°C) for more than 12 hours in a row, or in high humidity or heavy snow areas.
  5. Do not use a concentrated drain pipe. Use only the existing drain holes.
  6. Remove the rear inlet grille so snow does not build up on the rear fins.
  7. Keep the suction side facing a wall and do not expose it directly to wind. Use a baffle plate on the discharge side if wind is a problem.
  8. In heavy snowfall areas, raise the unit on a pedestal or build a large canopy.

Applies to: Outdoor units in areas with snow or low ambient

More heat pump guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Daikin DX6VS/DZ6VS outdoor unit installation & service reference, p. 9. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.