Daikin · Heat pump troubleshooting

Checking the outdoor or indoor pressure sensor

DX6VSDZ6VSDFVEDV**FEC

What is going on

The pressure sensor reads low or high side pressure and outputs a DC voltage that rises with pressure. Output range shown is 0 to 4 VDC for 0 to 800 PSIG.

Likely causes

  • Open or shorted sensor
  • Voltage outside the valid range

Check in this order

  1. With power on, connect a voltmeter across the sensor terminals between the black and white wires.
  2. Compare the reading with the voltage vs. pressure characteristic for the unit (1.5–3.0 ton outdoor, or 3.5–5.0 ton outdoor and indoor).
  3. Replace the sensor if it is open, shorted, or outside the valid voltage range.

Applies to: Outdoor unit (1.5–5.0 ton) and indoor unit pressure sensors

More heat pump guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Daikin DX6VS/DZ6VS service instructions SiUS612209EB, p. 17. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.