Daikin · Heat pump troubleshooting

Checking the high pressure switch

DX6VSDZ6VS

What is going on

The high pressure switch opens the control circuit on abnormally high discharge pressure, before the compressor overloads. It does not reset automatically.

Likely causes

  • Open switch contacts
  • Broken or loose wiring at the PCB connection

Check in this order

  1. Disconnect power and wait for the high voltage to be cleared.
  2. Remove the wire on the PCB side of the switch.
  3. Use an ohmmeter across the PCB-side switch terminals.
  4. If the reading is not continuous, the circuit is open. Replace the switch if necessary.
  5. After a trip, turn main power off to reset the switch.

Applies to: High pressure switch on the outdoor unit control circuit

More heat pump guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Daikin DX6VS/DZ6VS service instructions SiUS612209EB, p. 16. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.