Daikin · Heat pump troubleshooting
Check thermistor, EEV coil and solenoid valve coil resistance (S-26)
What is going on
Outdoor units and EEV indoor units use thermistors for outdoor air, coil, liquid, discharge, defrost, suction, indoor gas and indoor liquid. The EEV and solenoid valves are coils that also have a resistance check.
Likely causes
- Open, shorted or out-of-range thermistor
- Open or shorted EEV coil
- Open or shorted solenoid valve coil
Check in this order
- Disconnect power to all equipment.
- Disconnect the thermistor connector from the control board.
- Connect an ohmmeter across the thermistor terminals and compare with the thermistor resistance table. Replace if open, shorted or out of range.
- To check the EEV coil, disconnect the EEV cable from the control board and read resistance between the connector pins. The reading should be 40 to 50 Ω.
- To check the solenoid valve coil, disconnect the cable from the control board and read resistance between the connector pins. The reading should be 1,480 to 1,820 Ω.
Applies to: Outdoor units and EEV indoor units
More heat pump guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Daikin SiUS612209EA service instructions, p. 21. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.