Check indoor or outdoor pressure sensor
What is going on
The outdoor and indoor pressure sensors read low or high side pressure as a DC output voltage. The voltage-versus-pressure curve is a graph in the manual and its values are not listed as text here.
Likely causes
- Sensor open or shorted
- Output voltage outside the valid range
Check in this order
- Turn power ON and note that line voltage is present.
- Connect a voltmeter across the sensor terminals between the black and white wires.
- Compare the reading with the voltage versus pressure characteristic for the unit (1.5 to 3.0 ton or 3.5 to 5.0 ton and indoor unit).
- Replace the sensor if it is open, shorted or outside the valid voltage range.
Applies to: Outdoor units 1.5-3.0 ton and 3.5-5.0 ton; indoor units
More heat pump guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Daikin SiUS612209EA service instructions, p. 17. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.