Daikin · Heat pump troubleshooting

Check indoor or outdoor pressure sensor

DX6VSDZ6VSDV**FEC

What is going on

The outdoor and indoor pressure sensors read low or high side pressure as a DC output voltage. The voltage-versus-pressure curve is a graph in the manual and its values are not listed as text here.

Likely causes

  • Sensor open or shorted
  • Output voltage outside the valid range

Check in this order

  1. Turn power ON and note that line voltage is present.
  2. Connect a voltmeter across the sensor terminals between the black and white wires.
  3. Compare the reading with the voltage versus pressure characteristic for the unit (1.5 to 3.0 ton or 3.5 to 5.0 ton and indoor unit).
  4. Replace the sensor if it is open, shorted or outside the valid voltage range.

Applies to: Outdoor units 1.5-3.0 ton and 3.5-5.0 ton; indoor units

More heat pump guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Daikin SiUS612209EA service instructions, p. 17. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.