Daikin · Heat pump troubleshooting
Check high pressure switch
What is going on
The high pressure switch senses compressor discharge pressure. It opens the control circuit on abnormally high condensing pressure, before the compressor overloads. It is not auto-reset.
Likely causes
- Abnormally high condensing pressure
- Open switch contacts or broken wiring
Check in this order
- Disconnect all power.
- Remove the wire from the PCB side of the high pressure switch.
- With an ohmmeter, check continuity across the switch terminals on the PCB side.
- If there is no continuity, the circuit is open. Replace the switch if necessary.
- After a trip, turn main power OFF to reset the switch.
Applies to: Outdoor units DX6VS / DZ6VS
More heat pump guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Daikin SiUS612209EA service instructions, p. 16. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.