Daikin · Heat pump troubleshooting
Check for non-condensables (S-114)
What is going on
Non-condensables are gas trapped in the system that does not condense. Check when pressures look wrong.
Likely causes
- Air or other non-condensable gas in the refrigerant circuit
Check in this order
- Shut the system down and let pressures equalize for at least 15 minutes.
- Compare the pressure with the saturation temperature of the coldest coil, since most refrigerant collects there.
- If the pressure reads a higher temperature than the coil, non-condensables are present.
- Remove the charge, replace or install a liquid line drier, evacuate and recharge.
Applies to: Outdoor units DX6VS / DZ6VS
More heat pump guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Daikin SiUS612209EA service instructions, p. 23. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.