Daikin · Heat pump troubleshooting

Check for non-condensables (S-114)

DX6VSDZ6VS

What is going on

Non-condensables are gas trapped in the system that does not condense. Check when pressures look wrong.

Likely causes

  • Air or other non-condensable gas in the refrigerant circuit

Check in this order

  1. Shut the system down and let pressures equalize for at least 15 minutes.
  2. Compare the pressure with the saturation temperature of the coldest coil, since most refrigerant collects there.
  3. If the pressure reads a higher temperature than the coil, non-condensables are present.
  4. Remove the charge, replace or install a liquid line drier, evacuate and recharge.

Applies to: Outdoor units DX6VS / DZ6VS

More heat pump guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Daikin SiUS612209EA service instructions, p. 23. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.