Daikin · Heat pump troubleshooting

Check for compressor burnout (S-115)

DX6VSDZ6VS

What is going on

A burned-out compressor breaks down refrigerant, oil and motor insulation into acids and sludge. Confirm the burnout with an oil acid test before cleaning the system.

Likely causes

  • Compressor overheating and burnout
  • Acidic oil from insulation breakdown

Check in this order

  1. Attach a refrigerant hose to the liquid line drill valve and recover and dispose of the refrigerant following EPA rules.
  2. Remove the compressor and take an oil sample from the gas stub.
  3. Run an oil acid test. If the oil is not acidic, the burnout did not happen or is very mild.
  4. If the acid level is unacceptable, clean the system using the clean-up drier method.
  5. Do not let sludge or oil touch the skin.

Applies to: Outdoor units DX6VS / DZ6VS

More heat pump guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Daikin SiUS612209EA service instructions, p. 23. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.