Daikin · Heat pump troubleshooting
Check for compressor burnout (S-115)
What is going on
A burned-out compressor breaks down refrigerant, oil and motor insulation into acids and sludge. Confirm the burnout with an oil acid test before cleaning the system.
Likely causes
- Compressor overheating and burnout
- Acidic oil from insulation breakdown
Check in this order
- Attach a refrigerant hose to the liquid line drill valve and recover and dispose of the refrigerant following EPA rules.
- Remove the compressor and take an oil sample from the gas stub.
- Run an oil acid test. If the oil is not acidic, the burnout did not happen or is very mild.
- If the acid level is unacceptable, clean the system using the clean-up drier method.
- Do not let sludge or oil touch the skin.
Applies to: Outdoor units DX6VS / DZ6VS
More heat pump guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Daikin SiUS612209EA service instructions, p. 23. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.