Daikin · Heat pump troubleshooting

Check compressor efficiency (S-104)

DX6VSDZ6VS

What is going on

Low compressor efficiency means the compressor cannot pump vapor well. Confirm the charge is correct before condemning the compressor.

Likely causes

  • Broken or damaged compressor
  • Incorrect refrigerant charge (check first)

Check in this order

  1. Attach gauges to the high and low side of the system.
  2. Start the system and run CHARGE MODE.
  3. If the charge is correct and the readings show low high-side pressure, high low-side pressure, low temperature difference across the coil, and low compressor amp draw, the compressor is faulty. Replace it.

Applies to: Outdoor units DX6VS / DZ6VS

More heat pump guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Daikin SiUS612209EA service instructions, p. 22. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.