Daikin · Heat pump troubleshooting
Check compressor efficiency (S-104)
What is going on
Low compressor efficiency means the compressor cannot pump vapor well. Confirm the charge is correct before condemning the compressor.
Likely causes
- Broken or damaged compressor
- Incorrect refrigerant charge (check first)
Check in this order
- Attach gauges to the high and low side of the system.
- Start the system and run CHARGE MODE.
- If the charge is correct and the readings show low high-side pressure, high low-side pressure, low temperature difference across the coil, and low compressor amp draw, the compressor is faulty. Replace it.
Applies to: Outdoor units DX6VS / DZ6VS
More heat pump guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Daikin SiUS612209EA service instructions, p. 22. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.