Daikin · Heat pump troubleshooting

Capacitor voltage check (Check No.21)

FTXM-W/V

What is going on

Checks that the main capacitor voltage is safe before working on the outdoor unit.

Check in this order

  1. Turn the circuit breaker off and wait 10 minutes.
  2. 09/12 class measure the voltage between DC_P2 (+) and DC_N2 (-). It must be 50 V or less.
  3. 18/24 class measure the voltage between FU2 and DC-. It must be 50 V or less.
  4. The test points may be coated. Make firm contact with the multimeter probes.

Applies to: Outdoor unit DC capacitor

More heat pump guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Daikin Inverter Pair FTXM-W/V service manual, p. 156. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.