Calculating refrigerant charge from line set length

DX6VSDZ6VSDZ6VSA

What is going on

Total charge (A) equals the factory charge (B) plus the additional charge for the line set (C). The factory charge may differ from the nameplate; if so, calculate C so the total still matches the table. Values are per 5 ft of line; interpolate linearly between listed lengths. Refer to the elbow equivalent length page for fittings.

Check in this order

  1. Identify the indoor coil type, liquid and suction pipe diameters, and actual line set length.
  2. Read the total (A) and additional (C) charge from the table for that combination.
  3. Interpolate linearly between lengths that are not listed.
  4. Use the factory charge (B) as stated for the unit; if it differs from the nameplate, adjust C to keep total A.
  5. Add the additional charge (C) to the factory charge for the total charge.

Applies to: Charge calculation for line set length

More heat pump guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Daikin DX6VS/DZ6VS installation manual (3P731493-1), p. 23-24. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.