Amber STATUS or green COMM light not on

What is going on

On the Carrier Infinity 18VS (25VNA8), two small lights on the outdoor AOC board tell you most of what you need to know before any meter comes out. In my experience, a dead amber STATUS light with power present nearly always means the board is bad. The green COMM light is more forgiving because on a non-communicating thermostat it is supposed to be off. So check what kind of control you have before you condemn anything. Wall control code 179 is the other clue.

Likely causes

  • AOC board failure
  • No communication with the indoor unit or wall control
  • Non-communicating thermostat, where the COMM light is normally off
  • A and B communication wires open, shorted or swapped

Check in this order

  1. With power to the outdoor unit the amber STATUS light must be on or flashing, if it is completely off, check that the unit has voltage, then replace the AOC board
  2. Communicating systems the green COMM light should be on steady once the indoor unit and Infinity control talk to it, it goes off after 2 minutes without communication
  3. If the A and B wires are connected and the indoor unit communicates but COMM stays off, replace the AOC board
  4. Check the A and B wires at both ends for tight, correct connections
  5. Wall control code 179 means lost communication with the outdoor AOC, the AOC or inverter may need replacing
  6. Kill power at the disconnect before checking or changing wiring on the board

Applies to: Carrier Infinity 18VS variable speed heat pump 25VNA8

More heat pump guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Carrier 25VNA8 / 24VNA9 Service Manual, Communication and Status Function Lights p.8; LED tables p.27-28. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.