Carrier · Heat pump troubleshooting
Adding refrigerant for longer line sets
What is going on
The outdoor unit holds a factory charge. Longer line sets need extra refrigerant.
Check in this order
- Use the service port on the outdoor unit low pressure valve to charge.
- Calculate the extra refrigerant from Table 6 using the actual line length.
- Check the factory charge limit of 25 ft (8 m) against the installed line length.
- Record the line length and added refrigerant capacity.
Applies to: Outdoor unit refrigerant charge
More heat pump guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: D5CURA installation manual, p. 29 and p. 30. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.