Carrier · Heat pump troubleshooting

Adding refrigerant for longer line sets

D5CURA

What is going on

The outdoor unit holds a factory charge. Longer line sets need extra refrigerant.

Check in this order

  1. Use the service port on the outdoor unit low pressure valve to charge.
  2. Calculate the extra refrigerant from Table 6 using the actual line length.
  3. Check the factory charge limit of 25 ft (8 m) against the installed line length.
  4. Record the line length and added refrigerant capacity.

Applies to: Outdoor unit refrigerant charge

More heat pump guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: D5CURA installation manual, p. 29 and p. 30. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.