Carrier · Heat pump troubleshooting
9K/12K/18K evaporator disassembly
What is going on
Procedure to open up the indoor evaporator section on the 9K, 12K and 18K sizes and remove the refrigerant sensor.
Check in this order
- Remove the 2 screws holding the pipe clamp board.
- Remove the 4 screws of the evaporator connecting board, then take the board out.
- Remove the 1 screw of the evaporator fixing hanger, then take the hanger off.
- Remove the 4 screws holding the refrigerant sensor, then remove the sensor.
Applies to: 9K, 12K and 18K indoor units
More heat pump guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: D5FSCAH / D5FLCAH service manual, p. 64-65. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.