485 communication fault between indoor and outdoor units (S1, S2)

D5FUAA

What is going on

Troubleshooting for the 485 communication link on the S1 and S2 signal wires. Parts to have ready: signal wires, magnet ring, indoor PCB, outdoor PCB. The flowchart on the page is not fully clear, so steps follow the logical order of the checks shown.

Likely causes

  • Broken signal wire
  • Signal wire not shielded or shield not grounded
  • Electrical interference from nearby lamps or power transformers
  • Signal wire too long
  • Signal wires not inserted properly on the PCB
  • Faulty indoor main PCB
  • Faulty outdoor main PCB

Check in this order

  1. Check whether the signal wire is broken and replace it if needed.
  2. Check whether the signal wire is shielded cable and whether the shield is grounded. Use shielded cable and ground the shield if not.
  3. Check for interference, such as too many lamps or power transformers, or a signal wire that is too long. Remove the interference or add a magnet ring on the power wire.
  4. Check that the signal wires are fully inserted on the PCB. Pull out and reinsert them.
  5. Power off, then restart the unit 2 minutes later.
  6. If the error persists, replace the indoor main PCB.
  7. If the error still persists, replace the outdoor main PCB.

Applies to: D5FUAA

More heat pump guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Carrier D5FUAA service manual, p. 41. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.