Carrier · Heat pump troubleshooting
4-way valve check
What is going on
Check the 4-way reversing valve coil voltage and resistance.
Likely causes
- Wrong coil voltage for the operating mode
- Faulty valve coil
Check in this order
- Power on and measure the coil voltage with a digital tester.
- In cooling the voltage should be 0 V; in heating it should be about equal to the supply voltage.
- If the voltage is outside this range, the PCB is faulty and must be replaced.
- Turn off the power and measure the coil resistance; it should be 1.8 to 2.5 kΩ.
Applies to: D5CURA outdoor unit 4-way valve
More heat pump guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: D5CURA service manual, p. 64. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.