Tank placement and condensate piping

Large Commercial Condensate Neutralizer Tank

What is going on

Install the neutralizer tank so condensate flows by gravity from the appliance into the tank and on to the drain, with no backflow and no flue gas leakage.

Check in this order

  1. Set the tank on a secure, level base.
  2. Make sure the tank inlet and outlet are lower than the appliance condensate drain.
  3. Connect the appliance condensate drain to the tank inlet using corrosion-resistant piping.
  4. Keep the condensate line out of any area exposed to freezing temperatures.
  5. Protect the piping from foot or vehicle traffic where damage is possible.
  6. Check that the piping has no air pockets and that condensate flows freely into the tank and out to the drain.
  7. Install a trap on every condensate drain to stop flue gas leakage.
  8. Make sure the connection between appliance and tank prevents condensate backflow into the appliance.
  9. Check local water authority rules before discharging treated condensate to the drain or sewer.
  10. Install unions at the inlet and outlet so the tank can be removed quickly when changing media.

Applies to: Large commercial condensate neutralizer tank, 7,000 MBTU/hr

More general guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Navien large commercial condensate neutralizer tank installation instructions, p. 1-2. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.