Navien · General troubleshooting

Backpressure from DHW recirculation

WEC

What is going on

With a DHW recirculation system, backflow can build pressure in the WEC. The freeze prevention drain relieves it.

Likely causes

  • Backflow from a DHW recirculation loop

Check in this order

  1. Install a check valve and expansion tank on the feedwater line before the water heater.
  2. If backpressure builds, drain through the NDI module freeze prevention water drain line.
  3. The drain runs for up to 1 hour.
  4. If backpressure persists, expect an error code and check the Installation & Operation Manual troubleshooting section.

Applies to: WEC600 with DHW recirculation

More general guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: WEC Series service manual, p. 13. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.