Navien · General troubleshooting
Tank location and drain slope
What is going on
Condensate flow depends on the tank sitting lower than the appliance drain. Backflow into the appliance must be prevented.
Likely causes
- Tank mounted at or above the appliance condensate drain port
- Outlet piping set so condensate can back up into the appliance
Check in this order
- Set the neutralizer tank on the floor below the appliance condensate drain port.
- Raise the appliance above the tank if the tank cannot be lowered.
- Make sure the bottom of the appliance condensate outlet is above the bottom of the tank outlet, unless a pump with integral check valve is installed.
- Install piping so no condensate can flow back into the appliance.
Applies to: Navien condensing appliances with neutralizer tank
More general guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Navien commercial neutralizer installation instructions, p. 1-2. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.