Navien · General troubleshooting
Replacing the TDS sensor on the inlet water pipe assembly
What is going on
Removes the TDS sensor from the T-adapter on the inlet water pipe assembly. Part of the inlet pipe section, so some steps in the manual are printed on the following page.
Check in this order
- Shut off the feedwater supply.
- Disconnect power to the WEC.
- Remove the 2 screws on each side of the front cover and set the cover aside.
- Remove the ground wire screw from the WEC case and unplug the circulation pump connector from the harness.
- Remove the pump adapters from the circulation pump.
- Remove the 4 pump bracket screws and lift the circulation pump assembly out of the WEC.
- Unclip the inlet water pipe assembly and pull out the CIP solenoid valve assembly.
- Unplug the connector from the CIP solenoid valve.
- Use a wrench to remove the TDS sensor connector from the harness, then remove the TDS sensor from the T-adapter.
- Install the new TDS sensor on the T-adapter and connect its connector to the harness.
- Reinstall the CIP solenoid valve assembly, clip it to the inlet water pipe, and secure the pump bracket with 4 screws.
- Fix the ground wire to the WEC case, connect the circulation pump connector, and reinstall the pump adapters.
- Align the front cover with the WEC and secure each side with 2 screws.
Applies to: WEC600
More general guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Navien WEC Series service manual, p. 104-106. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.