Navien · General troubleshooting
Replacing the pressure sensor
What is going on
Remove the back cover, disconnect the sensor, unscrew it from the outlet adapter, and fit the new sensor.
Check in this order
- Turn off the feedwater supply.
- Disconnect power to the WEC.
- Remove the back cover (see page 82).
- Remove the rubber cap and unplug the connector from the pressure sensor.
- Turn the pressure sensor counterclockwise and remove it from the outlet adapter.
- Install the new pressure sensor on the outlet adapter and turn it clockwise to tighten.
- Plug the harness connector into the pressure sensor and reinstall the rubber cap.
- Reinstall the back cover and secure it with 11 screws.
Applies to: WEC600
More general guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Navien WEC service manual, pp. 92-93. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.