Navien · General troubleshooting

Replacing the freeze prevention solenoid valve

WEC

What is going on

Remove the back cover, disconnect the valve and hoses, then fit the new solenoid valve and reconnect it.

Check in this order

  1. Turn off the feedwater supply.
  2. Disconnect power to the WEC.
  3. Remove the back cover (see page 82).
  4. Remove the 2 screws holding the freeze prevention solenoid valve and pull the valve out.
  5. Unplug the connector from the solenoid valve.
  6. Remove the 2 clips and detach the hoses from the solenoid valve.
  7. Connect the hoses to the new solenoid valve and secure the 2 clips.
  8. Plug the harness connector into the solenoid valve.
  9. Place the valve on the water treatment system and fasten it with 2 screws.
  10. Reinstall the back cover and secure it with 11 screws.

Applies to: WEC600

More general guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Navien WEC service manual, p. 96. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.