Navien · General troubleshooting

Replacing the CIP dosing pump

WEC

What is going on

Remove the CIP tank assembly to reach the CIP dosing pump, then reinstall the tank with the new pump.

Check in this order

  1. Turn off the feedwater supply.
  2. Disconnect power to the WEC.
  3. Remove the 2 screws on each side of the front cover and take the cover off.
  4. Remove the 4 screws holding the CIP tank, release the 2 clips on the dosing pump, and lift the CIP tank assembly out of the WEC.
  5. From the front of the CIP tank, remove the 2 screws holding the pump bracket and unplug the dosing pump connector from the harness. Then take the dosing pump out of the tank.
  6. Fit the new dosing pump to the tank with 2 screws in the pump bracket and reconnect its connector to the harness.
  7. Secure the 2 clips on the dosing pump, seat the CIP tank in the WEC, and fasten it with 4 screws.
  8. Line up the front cover screw holes and secure each side with 2 screws.

Applies to: WEC600

More general guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Navien WEC service manual, pp. 90-91. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.